Room automation station, ecos504/505
Model
EY-RC 504/505
How energy efficiency is improved
Powerful function modules in the ecos504/505 integrate the regulation of the room temperature, lighting and sunshading to create a comfortable room climate with minimum energy consumption
Features
- Part of the SAUTER modulo 5 system family
- Modular room automation station (AS) for up to eight rooms or eight flexible room segments
- BACnet/IP communication (EN ISO 16484-5) as BACnet Building Controller (B-BC)
- The ecoUnit 3 and ecoUnit 1 room operating units enable individual adjustment of the room climate
- Optimises energy consumption thanks to presence function, window contact monitoring, demand-controlled ventilation, control of lighting and window blinds, and time-dependent setpoint
- Function libraries for climate, lighting and sunshading
- Expansion bus for remote ecoLink modules, ecoUnit room operating units and EnOcean wireless interface
- KNX interface to connect KNX operating devices, sensors and actuators
- Integrated KNX tunnelling function (KNX/IP) for the commissioning of KNX with ETS
- DALI interface with DALI bus power supply for connecting DALI electronic ballasts (EB) and DALI sensors and push-buttons
- Web-based commissioning tool for DALI network
- Integrated tunnelling function for monitoring DALI communication via IP
- SMI interface (SMI/SMI LoVo) for activating SMI motors for sunshading (window blinds, roller shutters)
- Integrated tunnelling function for commissioning with SMI-easyMonitor
- RS‑485 half-duplex, galvanically isolated interface for Modbus/RTU, Modbus/ASCII
- Baud rate 600 to 115,200 bit/s with configurable RS-485 network resistors
- Modbus master with up to four simultaneous communication profiles
- Integrated tunnelling function for commissioning and monitoring with serial Modbus master tools
- Physical M-Bus interface and RS‑232 interface for external M-Bus level converters
- Supports M-Bus baud rates of 300 to 38,400 bit/s
- M-Bus master function with up to four simultaneous communication profiles
- Integrated tunnelling function for commissioning and monitoring with M-Bus tools
- Time programme and calendar function; data recording, control libraries
- Integrated (EY‑RC504F202 only) or licensable MQTT functionality (MQTT broker/client)
- Engineering/programming using SAUTER CASE Suite (based on IEC 61131-3)
- Integration into the building management system via BACnet/IP with Ethernet interface
Related
Similar Products
EY-RC 311
Room controller, ecos311
YCS 472, 474
Digital Services – Customer Portal
YCS 200...210
Mobile Building Services (MBS)
XAFP 100
Flow probe for ventilation ducts
VDL 010...050
2-way regulating valve for dynamic hydronic balancing, PN 25, Valveco compact
TSUP
Room-temperature transducer
TSP, TSFP, TSSP
Pneumatic room-temperature controller
TSHK 681, 682